R-ION

Programmable Controller

R-ION series products are programmable room controllers ideal for managing a wide range of individual building products such as fan-coil units and VAV boxes. Extremely flexible customization options are available thanks to configurable color touchscreen, full programmability, custom logo possibility and various style/color options. The unit has no on-board inputs & outputs, but is able to connect to a multitude of external IO, due to multiple communication ports and protocols. Integrated temperature sensor is standard in all versions. The unit can also be ordered in a temperature plus relative humidity sensing configuration. In addition to basic fan-speed and temperature settings, lighting controls can easily be integrated, as well as custom application specific functions (e.g. Do Not Disturb / Make Up Room buttons for hotel rooms).

Features

  • 3.5” resistive color touch-screen
  • Freely programmable
  • Fully customizable graphics
  • Powered by Sedona Framework
  • Integrated temperature sensor
  • Optional relative humidity sensor
  • Multiple communication ports
  • WIFI option
  • Belimo MP-Bus option
  • Dali (Digital Addressable Lighting Interface)
  • DMX driver available
  • Low profile, only 10.5 mm thick
  • Optional Input/output modules optimized for terminal units

Display / User Interface: 3.5” resistive color touch-screen. 65K colors. The display pages and user interface are freely customizable by a systems integrator. Multiple pages can be configured with various widgets for displaying / modifying values.
Communications: R-ION controllers support various industry standard protocols simultaneously. The main supervisory system communication (Port 1) is serial RS485 or wireless IP depending on basic version:

  • WIFI versions support BACnet IP, ModbusTcp (master and/or slave), Sox protocol.
  • Serial ports support BACnet MSTP (slave) and Modbus RTU (master and/or slave)

Optionally, one or more of the following auxilliary communication ports may be available:

  • Second RS485 port (Modbus & DMX drivers available)
  • Belimo MP-Bus
  • DALI (Digital Addressable Lighting Interface) port

FRAME STYLE 1

FRAME STYLE 2

DIAGRAMMA DI CONNESSIONE

R-MIO

Input Output Module for R-ION

R-MIO modules provide a compact input/output solution for Ontrol’s R-ION series programmable touch-screen room controllers. This combination greatly simplifies installation on the wall-unit side, as the IO module can be located close to the terminal unit being controlled, with only comms wiring into the wall unit. The mains powered versions eliminate the need for additional power-supplies or transformers further reducing cost and installation labor. R-MIO input/output modules are not independently communicating devices. They can only be used with the R-ION controllers.

uyqFeatures

  • Compact input/output module for the R-ION room controller
  • Designed for terminal-unit control
  • Mains or 24 Vac powered versions
  • Fused mains power output for field devices
  • 24 Vac aux. supply output for field devices (on some versions)
  • Two-wire combined comms and power connection to the R-ION controller

Fan-speed control:3 relays are provided specifically for 3-speed fan control. These relays can not be used independently.
Triac Outputs: 4 triac outputs are provided with flexble configuration options, allowing control of on/off thermoelectric (PWM) or floating actuators or relays. The triacs can be independently configured to control different loads. However, due to internal connections, all loads must be supplied from the same AC voltage. Floating (three-position) configuation requires use of two triacs.
Modulating Outputs: two 0-10VDC analog outputs are provided for controlling modulating valve or damper actuators.
Relay Output: a single relay output with 10 A rating is provided.
Digital Inputs: voltage-free contacts can be connected to the two digital input terminals.
Aux. supply output to field devices: some mains-powered versions provide 24 VAC output for fied devices such as valve and damper actuators.
Expansion port: one RK4 module can be connected to the device with a ribbon cable, providing 4 additional relay outputs

R-TIO

Input Output Module for R-ION

R-TIO modules provide a compact input/output solution for Ontrol’s R-ION series programmable touch-screen room controllers. This combination greatly simplifies installation on the wall-unit side, as the IO module can be located close to the terminal unit being controlled, with only communication wiring into the wall unit. The mains powered versions eliminate the need for additional power-supplies or transformers further reducing cost and installation labor. R-TIO also hosts a battery backed-up real-time-clock. Therefore, time schedules can be implemented directly on the device, fully configurable locally from the connected R-ION or remotely from a supervisory system. R-TIO input/output modules are not independently communicating devices. They can only be used with the Ontrol R-ION touch screen controllers. However, a Modbus communicating version (M-TIO) is also available for use on other systems.

Relay Outputs: 5 relay outputs are provided. Each relay can be used independently, and a specific set of three can be configured for 3-speed fan control.
Triac Outputs: 2 triac outputs are provided with flexible configuration options, allowing control of on/off thermoelectric (PWM) or floating actuators or relays. The triacs can be independently configured to control different loads. However, due to internal connections, all loads must be supplied from the same AC voltage. Floating (three-position) configuration requires use of both triacs.
Modulating Outputs: Four 0-10VDC analog outputs are provided for controlling modulating valve or damper actuators. Two of these can be configured to function as digital inputs.
Expansion port: up to two RK4 modules can be connected to the device with a ribbon cable, providing a total of 8 additional relay outputs.